Parameter changes do not become effective immediately in the device (eliminated from V3.3.2)

Corrected from:
PLC Designer V3.3.2

Behaviour of the new version?
During the OnlineChange, parameter changes are transferred to the devices immediately and also become effective immediately.



What happens?
Parameter changes carried out in the PLC project do not become effective immediately in the device.

When does the problem occur?
If device parameters of the i700 servo inverter, I/O1000 EtherCAT bus coupler EPM-S130 or I/O1000 CAN bus coupler EPM-S110 devices are changed offline in the PLC project, these changes are not transferred to the devices when logging in on the controller. This means that the parameter changes do not become effective immediately in the device at log-in.

Which products are affected?
PLC Designer from V3.3
i700 servo inverter
EPM-S110
EPM-S130

Diagnostics options?
None

Short-term measures/recommendations?
Restart the fieldbus, e.g. by resetting the controller.

Evaluation:
If parameters of devices connected to the controller are changed offline, they are not transferred automatically to the devices when going online. This requires a restart of the fieldbus.

URL for linking this AKB article: /en-de/go/akb/201208232/1/