Quick stop is without any effect in i700 Application Sample (corrected from V3.5)

Corrected from:
PLC Designer V3.5
Application sample i700 V0.1.0.2

Response of the new version?
The indices 0x6085/0 and 0x6885/0 (quick stop: deceleration) are set to the maximum value 2147483647 in the application sample for the i700 servo inverter.




Which products are affected?
PLC Designer V3.3
Application sample i700 V02.00

What happens?
The drive continues to rotate endlessly and with unchanged speed if the quick stop function is activated.

When does the problem occur?
The indices 0x6085/0 and 0x6885/0 * (quick stop: deceleration) are set to 0 in the application sample for the i700 servo inverter.

*) only available with double axis.

Diagnostic options?
None

Short-term measures/recommendations?
Change the parameter value from 0 to the max. value (2147483647).

Evaluation
Due to the quick stop deceleration set in the i700 application sample the i700 double servo inverter continues to rotate with unchanged speed if quick stop is set. The function restriction can be eliminated by changing the quick stop deceleration.