Corrected from:
PLC Designer V3.5
Response of the new version?
The SoftMotion node of axis A of an i700 double axis is available after a double axis of an i700 servo inverter has been inserted into a PLC Designer project.
Which products are affected?
PLC Designer from V3.3
What happens?
The SoftMotion node of axis A of the double axis is missing if a double axis of an i700 servo inverter has been inserted into a PLC Designer project.
When does the problem occur?
The response described above occurs if
? an i700 double axis is copied from a PLC Designer project and inserted into a new PLC Designer project
or
? an i700 double axis is exported from a PLC Designer project (menu item: Project>Export) and imported in a new PLC Designer project (menu item: Project>Import).
Diagnostic options?
None
Short-term measures/recommendations?
Insert the double axis of the i700 servo inverter manually into the new PLC Designer project and take over the parameter values from the already existing project by exporting/importing the device parameters.
Evaluation
It is not possible to copy or import a double axis of an i700 servo inverter from a PLC Designer project in another project.