Controller indicates fatal error after cold reset (corrected from V3.5)

Corrected from:
PLC Designer V3.5
Controller 3200 C
Controller p500

Response of the new version?
A cold reset carried out while the TCP server is running does not cause a fatal error anymore.




Which products are affected?
PLC Designer V3.3
Controller 3200 C
Controller p500

What happens?
The Controller indicates the following error message:
Application PLCV3Wince.exe encountered a serious error and must be shut down.


When does the problem occur?
The controller indicates a fatal error if a cold reset is triggered while the TCP server is running. The controller is booted correctly after mains switching.

Diagnostic options?
None

Short-term measures/recommendations?
Stop the TPC server before carrying out a cold reset. In order to do so, set the xEnable function block input of the TCP server to FALSE.

Evaluation
If a cold reset is carried out while the TCP server is running the controller triggers a fatal error.

URL for linking this AKB article: /en-de/go/akb/201300223/1/
森林舞会游戏