Eliminated from:
PLC Designer V3.3.2
Behaviour of the new version?
In order to save a project as a previous PLC Designer version, it is now possible to select the desired PLC version in the file type field of the 'Save as' dialog.
What happens?
If a PLC project is to be saved as a previous PLC Designer version there are only CoDeSys versions indicated in the 'Save as' dialog (menu item: File >Save project as).
When does the problem occur?
In the 'Save as' dialog the user can chose in the 'file type' field if the project is to be saved in the current PLC Designer format (project files or library files) or in the format of a previous CoDeSys version.
Which products are affected?
PLC Designer from V3.1
Possible diagnostics?
None.
Short-term measurements/recommendations?
Select the corresponding CoDeSys version in order to save a PLC project in the format of a previous PLC Designer version:
PLC Designer V3.0 corresponds to CoDeSys V3.4 SP1
PLC Designer V3.1 corresponds to CoDeSys V3.4 SP3 Patch1
PLC Designer V3.2 corresponds to CoDeSys V3.4 SP4
Evaluation:
In order to save a PLC project as a previous PLC Designer version the corresponding CoDeSys version has to be selected in the 'Save as ' dialog.