What happens?
The PLC Designer cannot find the CAN nodes connected.
When does the problem occur?
The search for CAN nodes (context menu: 'Scan devices') via the CANopen Manager MC-CAN2 inserted in the device tree is not supported.
Which products are affected?
PLC Designer from V3.0
Possible diagnostics?
None.
Short-term measures/recommendations?
Insert the nodes connected to the CAN bus manually by using the CANopen Manager context menu 'Scan devices'.
Evaluation:
The device search for CAN nodes is not supported by the PLC Designer. CAN nodes with which the controller shall communicate are to be connected manually to the CANopen Manager.