Eliminated as of:
PLC Designer V3.3
Behaviour of the new version?
The measured values of the EPM-S404 are correctly displayed on the tab.
What happens?
In the PLC Designer, incorrect measured values are displayed on the 'Parameters' tab of the EPM-S404 module.
When does the problem occur?
The above-described problem occurs if all channels are set to '3000 Ohm two-wire' and no resistor is connected.
Possible diagnostics:
Compare the values on the tab with the values in the process image.
Short-term measures/recommendations:
Ignore the measured values displayed on the 'Parameters' tab. The values in the process image are correct.
Assessment:
Due to the function restriction, incorrect measured values are displayed for the EPM-S404 IO1000 module on the 'Parameters' tab. The values in the process image, i.e. the values used by the controller, are correct.