Corrected from: PLC Designer V3.12
Response of the new version:
When copying/moving modules below the CAN bus coupler (EPM-S110) or the EtherCAT bus coupler (EPM-S130), the parameters of the modules will remain unchanged.
What happens?
The parameters of the I/O system 1000 modules are reset to their standard values.
When does the problem occur?
When copying/moving modules below the CAN bus coupler (EPM-S110) or the EtherCAT bus coupler (EPM-S130), the parameters of the corresponding modules are reset to their standard values.
Which products are affected?
PLC Designer V3.2 and higher
EPM-S110 (CAN bus coupler)
EPM-S130 (EtherCAT bus coupler)
Possible diagnostics:
Check the parameters of the I/O modules after moving/copying the modules.
Short-term measures/recommendations:
Select the I/O module parameters once again after moving/copying the modules.
Evaluation:
When moving/copying I/O modules in the PLC Designer, the module parameters are reset to their standard values.