Parameters of the I/O 1000 modules are reset (corrected from V3.12)

Corrected from:
PLC Designer V3.12
 
Response of the new version:
When copying/moving modules below the CAN bus coupler (EPM-S110) or the EtherCAT bus coupler (EPM-S130), the parameters of the modules will remain unchanged.
 
What happens?
The parameters of the I/O system 1000 modules are reset to their standard values.

When does the problem occur?
When copying/moving modules below the CAN bus coupler (EPM-S110) or the EtherCAT bus coupler (EPM-S130), the parameters of the corresponding modules are reset to their standard values.

Which products are affected?
PLC Designer V3.2 and higher
EPM-S110 (CAN bus coupler)
EPM-S130 (EtherCAT bus coupler)

Possible diagnostics:
Check the parameters of the I/O modules after moving/copying the modules.

Short-term measures/recommendations:
Select the I/O module parameters once again after moving/copying the modules.

Evaluation:
When moving/copying I/O modules in the PLC Designer, the module parameters are reset to their standard values.

URL for linking this AKB article: /en-de/go/akb/201301772/1/