Eliminated from:
PLC Designer V3.6
8400 TopLine frequency inverter
Behaviour of the new version:
When updating an 8400 TopLine from version 1.0.0.x to V2.0.0.x, the complete PDO mapping is transferred.
What happens?
In case of the 8400 TopLine frequency inverter, the PDO mapping is not transferred completely. The status and control word are maintained, the other PDO objects are not linked anymore.
When does the problem occur?
The response described above occurs if an 8400 TopLine 1.0.0.x is updated to version 2.0.0.x.
Which products are concerned?
PLC Designer from V3.0
8400 TopLine frequency inverter
Possible diagnostics:
None
Short-term measures/recommendations:
Remove the 8400 TopLine frequency inverter from the PLC Designer project and then reinsert it.
Evaluation:
Updating an 8400 TopLine causes an incomplete CAN mapping.