Which products are affected?
PLC Designer from V3.5
Servo Inverter i700
What happens?
After an i700 axis in the PLC project has been updated, indices are missing in the mapping although it is the standard mapping.
When does the problem occur?
The response described above occurs if an i700 servo inverter V1.2.x.x is updated to version V1.3.x.x.
Diagnostic options?
None
Short-term measures/recommendations?
? Save the parameter set of the i700 servo inverter via the menu item 'Project?Device parameters?Export device parameters'.
? Afterwards, delete the i700.
? Insert an i700 with the new version in the device tree.
? Import the parameter set exported before.
Evaluation
When an i700 servo inverter is updated in the PLC project, the mapping is not completely transferred.