Eliminated from:
PLC Designer V3.6
Behaviour of the new version:
When using the Easy Starter to store the parameters in the controller, no error message appears.
What happens?
When the parameters in the controller are saved with the EASY Starter, the 'Error' error message appears.
When does the problem occur?
The response described above can occur if i700 servo inverters or I/O 1000 bus couplers EPM-S130 in the PLC Designer project are deactivated.
Which products are concerned?
PLC Designer from V3.3
Possible diagnostics:
Before downloading, check the project for deactivated i700 or EPM-S130.
Short-term measures/recommendations:
Before downloading the project, execute 'Clean all' (menu Build>Clean all).
Evaluation:
Deactivated devices in the PLC project cause an error message when the parameter set in the controller is saved with the EASY Starter.