i700 reports the error message: FoE par001.i7psf - invalid parameter (disk full) (eliminated from PLC Designer V3.6)

Eliminated from:
PLC Designer V3.6
 
Behaviour of the new version:
Opening and updating projects and subsequently going online does not cause any errors.
 
What happens?
The logbook provides the following messages:
? L_i700_SM_3 (1004): FoE par001.i7psf - 'invalid parameter'.
? FoE par001.i7psf - 'FoE error - data carrier full'.
But the program starts without any problems.

When does the problem occur?
The response described above occurs if the i700 servo inverter is used in a project which is updated after being opened and then an online connection is established.

Which products are concerned?
PLC Designer from V3.3

Possible diagnostics:
None

Short-term measures/recommendations:
After updating a project, Lenze recommends to clean the project in the PLC Designer (menu item Build>Clean all).

Evaluation:
After updating a project that has just been opened, error messages may appear in the logbook which, however, do not have any negative effects.