Eliminated from:
PLC Designer V3.6
Behaviour of the new version:
Opening and updating projects and subsequently going online does not cause any errors.
What happens?
The logbook provides the following messages:
? L_i700_SM_3 (1004): FoE par001.i7psf - 'invalid parameter'.
? FoE par001.i7psf - 'FoE error - data carrier full'.
But the program starts without any problems.
When does the problem occur?
The response described above occurs if the i700 servo inverter is used in a project which is updated after being opened and then an online connection is established.
Which products are concerned?
PLC Designer from V3.3
Possible diagnostics:
None
Short-term measures/recommendations:
After updating a project, Lenze recommends to clean the project in the PLC Designer (menu item Build>Clean all).
Evaluation:
After updating a project that has just been opened, error messages may appear in the logbook which, however, do not have any negative effects.