Red triangles on I/O modules on the backplane bus of the controller (eliminated from V3.6)

Eliminated from:
PLC Designer V3.6
 
Behaviour of the new version:
If additional devices are added on the backplane bus of the controller particular I/O 1000 compound modules (e.g. L_SMC_FreeEncoder), red triangles are no longer displayed.
 

?What happens?
To some I/O 1000 compound modules, additional devices can be added (e.g. L_SMC_FreeEncoder) on the backplane bus of the controller. Online, these devices are indicated by red triangle symbols. The module function is not impaired by this.

When does this behaviour occur?
The above-described behaviour may occur if when extracting a project archive (menu File > Project Archive > Extract Archive) created with a PLC Designer version lower than V3.5, the "L_IOM_IOModules" library V3.1.1.0 was installed in the Library Repository.
 
Which products are concerned?
PLC Designer from V3.5.1
L_IOM_IOModules library V3.1.1.0
 
Short-term measures:
Reinstall the "L_IOM_IoModules" library in the Library Repository. For this, proceed as follows:
  1. Unpack the attached zip file L_IOM_IoModules.zip (21.2kB) on your PC.
  2. For this, open the Library Repository in the PLC Designer (menu Tools > Library Repository).
  3. Click <Install> and select the unpacked library L_IOM_IOModules.compiled-library.
  4. Click <Open>. The library will be reinstalled in the Library Repository.
Evaluation/recommendations:
In online mode, red triangle symbols are displayed on the I/O 1000 compound modules on the backplane bus of the Lenze controller. The function restriction may occur after extracting an old project archive. The function of the modules is not affected by this.

URL for linking this AKB article: /en-de/go/akb/201304814/1/