Corrected from: PLC Designer V3.12
Response of the new version:
Both online and offline parameter access via the "All parameters" tab of the I/O 1000 CANopen bus coupler (EPM-S110) and the "Modules" tab of the I/O modules connected to the bus coupler is possible.
What happens?
Online parameter access via the "All parameters" tab of the I/O 1000 CANopen bus coupler (EPM-S110) and the "Modules" tab of the I/O modules connected to the bus coupler is not possible. When logging in, the parameter set of the bus coupler selected offline is transferred to the controller and thus to the bus coupler.
When does this behaviour occur?
The above-described behaviour occurs after logging in to the L-force c300 or p300 controller with the PLC Designer.
Which products are affected?
PLC Designer V3.8 and higher
EPM-S110 (I/O 1000 CANopen bus coupler)
L-force c300, p300 controller
Short-term measures/recommendations:
None
Evaluation:
With the PLC Designer, online read or write access to the parameters of the I/O 1000 CANopen bus coupler is not possible. Parameter sets created offline are, however, transferred to the controller and to the bus coupler.