Error message when creating the boot project (corrected from V3.9)

Corrected from: 
PLC Designer V3.9
p500 panel controller V3.9
 
Response of the new version:
When creating the boot project there is enough memory space available for the application.
 
What happens?
The following error message appears when creating the boot project:
No boot project possible in this state: Not enough memory space for application. Complete full download first.
 
When does this behaviour occur?
The above error message may sporadically occur in the case of frequent online changes in which the variable declaration is changed.
 
Which products are affected?
PLC Designer V3.8 and higher
L-force p500 controller V3.7 and higher
 
Short-term measures/recommendations:
When the error message is displayed, perform a reset origin on the controller (menu Online>Reset Origin). Log out from the controller, log in to it again, and recreate the boot project.
 
Evaluation:
So far, this function restriction could only be detected with the L-force p500 controller. After a reset origin, the boot project can be properly created.

URL for linking this AKB article: /en-de/go/akb/201400213/1/