?Corrected from:
PLC Designer V3.9
Response of the new version:
In the VisualizationManager, you can also use a style with "gradient". In this case, no compilation errors will occur.
What happens?
When compiling the PLC Designer project, the following error message appears repeatedly:
"Device does not support gradient style"
When does this behaviour occur?
The error messages occur when compiling a PLC project, if a visualisation with WebVisualization is used ("L-force Controller target system ... + WebVisualization (Lenze)") and a style with "gradient" is selected on the "Settings" tab of the VisualizationManager.
Which products are affected?
PLC Designer up to V3.8
Short-term measures:
Do not change the style configuration of the "VisualizationManager" in the PLC project. Maintain the "Default" setting.
Evaluation/recommendations:
In the "Configuration style" field in the VisualizationManager you can select a style which will then be applied to all visualisation pages. If you select a style that supports colour gradients, error messages will appear when compiling the PLC project.