Corrected from: PLC Designer V3.12
Response of the new version:
Files with the file name extension "CSV" can be transferred from the PLC Designer to the Lenze Controller.
What happens?
The PLC Designer does not transmit all files via file transfer ("Files" tab) to the Controller.
When does this behaviour occur?
Files with the file name extension "CSV" cannot be transferred via file transfer from the PLC Designer to the Lenze Controller.
Which products are affected?
L-force 3200C Controller V3.0 and higher
L-force p500 Controller V3.3 and higher
PLC Designer V3.0 and higher
Short-term measures:
Either transfer the CSV files via FTP or use an SD card reader and directly write the files to the SD card.
Evaluation/recommendations:
CSV files contain values that are separated by separators (e.g. data of a spreadsheet program). If such a file is on the SD card of the Lenze Controller, the values can be accessed from the Controller's PLC program. Due to this function restriction, it is not possible to transfer CSV files via file transfer from the PLC Designer to the Controller or its SD card. Alternative solutions are described in the section "Short-term measures".