Dead time and baud rate of SSI module cannot be changed (corrected from V3.10)

Corrected from:
PLC Designer V3.10
 
Response of the new version:
The parameters for dead time and baud rate of the I/O 1000 EPM-S604 module (SSI) can be set even if the module is connected to the backplane bus of the controller.
 
What happens?
Dead time and baud rate of the I/O 1000 EPM-S604 module (SSI) cannot be changed.
 
When does this behaviour occur?
If the I/O 1000 EPM-S604 module (SSI) is connected to the backplane bus of the controller, it is not possible to change the parameters for dead time and baud rate. If the values are changed offline, they are reset to the default values when going online.
If the values are changed online, they are not accepted in the I/O 1000 module. After changing the tab, the default values are displayed again.
 
Which products are affected?
PLC Designer V3.0 and higher
EPM-S604 (SSI)
 
Short-term measures:
Only connect SSI encoders to the I/O 1000 EPM-S604 module that support the default values for dead time (64?s) and baud rate (125kHz), if the I/O module is connected to the backplane bus of the controller.
 
Evaluation/recommendations:
If the I/O 1000 EPM-S604 module (SSI) is connected to the backplane bus of the controller, you can only connect SSI encoders to the I/O module which support a certain dead time and baud rate.

URL for linking this AKB article: /en-de/go/akb/201500027/1/