Start parameters are reset when updating device (corrected from V3.12)

Corrected from:
PLC Designer V3.12
 
Response of the new version:
When updating EtherCAT slaves in the project tree, the values of the start parameters will not be changed. 
 
What happens?
The start parameters of an EtherCAT slave are reset to their standard values.
 
When does this behaviour occur?
When updating an EtherCAT slave in the project tree of the PLC Designer, the start parameters are reset to the standard values specified in the device description. This does not concern start parameters created additionally.
 
Which produts are affected?
PLC Designer V3.0 and higher
 
Short-term measures/recommendations: 
Check the start parameters after updating an EtherCAT slave in the device tree of the PLC Designer.
 
Evaluation:
When updating an EtherCAT slave, the selected start parameters of the slave are reset to their standard values. Updates are required if e.g. a slave with a later firmware is to be used in the PLC project.

URL for linking this AKB article: /en-de/go/akb/201500423/1/