After updating to V3.10, many parameters are displayed online with the value "210" (corrected from V3.13)
Corrected from: PLC Designer V3.13
Response of the new version:
After logging in, the FAST Motion parameters have the set value. The dialog requesting users to execute the 'Clean all' command no longer appears.
What happens?
The FAST Motion parameters have an invalid value (e.g. all FAST Motion parameters have the value 210).
From PLC Designer V3.12, a dialog appears requesting users to execute the Build>Clean all menu command.
When does this behaviour occur?
The above-described behaviour may occur sporadically when downloading a PLC project after changing it (Online>Login menu command).
Which products are affected? PLC Designer from V3.10
Short-term measures/recommendations:
Execute the Build>Clean all menu command and download the project once again to the controller.
Evaluation: After downloading a project with the PLC Designer,the FAST Motion parameters may sporadically have an incorrect value. A workaround is described under 'Short-term measures'.