CODESYS SVN is not completely supported (corrected from V3.15)

Corrected from:
PLC Designer V3.15
 
Response of the new version:
The CODESYS SVN software versioning system from the CODESYS Store can be used without restrictions in the PLC Designer.
 
What happens?
  • The parameter values of the i700 servo inverter, the I/O 1000 CANopen bus coupler (EPM-S110), the I/O 1000 EtherCAT bus coupler (EPM-S130), and FAST Motion are reset to their default values.
  • The error dialog 'The project is corrupt. Please contact Lenze' appears.
When does this behaviour occur?
The above-described behaviour occurs if the CODESYS SVN software versioning system has been installed in the PLC Designer and is used.
 
Which products are affected?
PLC Designer from V3.2
 
i700 servo inverter
EPM-S110 (I/O 1000 CANopen bus coupler)
EPM-S130 (I/O 1000 EtherCAT bus coupler)

Short-term measures/recommendations?
Do no use the CODESYS SVN software versioning system from the CODESYS Store in the PLC Designer.

Evaluation:
When using the CODESYS SVN software versioning system, the parameter values of the i700, the I/O 1000 system and FAST Motion are reset to their default values and an error message appears. CODESYS SVN is not part of the PLC Designer delivery package and has to be purchased from 3S-Smart Software Solutions GmbH.

URL for linking this AKB article: /en-de/go/akb/201500795/1/