What happens?
Although no parameters were changed, the parameter comparison dialog appears when logging in to the controller. Under "Details", no differences can be seen.
Example:
When does this behaviour occur?
The behaviour occurs when the PLC Designer is used to transfer a PLC project to the controller. After this, log out and log in is performed with the PLC Designer.
The behaviour may occur with the following parameters:
- Position controller: Output signal limitation (0x2982 | 0x3182)
- Speed offset (0x60B1 | 0x68B1)
- Speed limitation: Upper speed limit (0x2946:1 | 0x3146:1)
- Speed limitation: Lower speed limit (0x2946:2 | 0x3146:2)
Which products are affected?
PLC Designer from version V3.12
Short-term measures:
Ignore the message if the values indicated under "Details" are identical.