VisiWinNET data is no longer available after switching the mains for the controller (corrected with V3.15.2)

Corrected from:
3231 C controller V3.15.2
 
Response of the new version:
VisiWinNET data is no longer deleted. 
 
What happens?
After switching the mains for the Lenze controller, the following data from VisiWinNET is no longer available:
  • Historical Alarms
  • Recipes
  • Trends
  • New user created at runtime
  • Changed passwords at runtime 
When does this behaviour occur?
The above-described behaviour occurs if individual data directories (e.g. trends) of the VisiWinNET project are empty.  
 
Which products are affected?
VisiWinNET (all versions)
3231 C controller from V3.12, V3.13, V3.14, V3.15, V3.15.1
 
Short-term measures:
Use controllers with firmware version V3.13.1 or lower than V3.12. 
 
Evaluation/recommendations:
After switching the mains for the controller, data of the VisiWinNET visualisation may no longer be available. If the function restrictions occurs, please contact Lenze.