Corrected from:
PLC Designer V3.15
Response of the new version:
Boot projects can be created even if the parameter value of a FAST Motion parameter has been changed online. The menu item 'Online>Create boot application for L-force controller' remains active.
What happens?
The PLC Designer is connected online with the controller. Since the menu item 'Online>Create boot application for L-force controller' is deactivated, it is not possible to create a boot project.
When does this behaviour occur?
If the PLC Designer is logged in to the controller and the parameter value of a FAST Motion parameter (of a motion axis or axis group) has been changed, the menu item 'Online>Create boot application for L-force controller' is deactivated.
Which products are affected?
PLC Designer V3.14
Short-term measures:
Disconnect the connection with the controller and log in again.
Evaluation/recommendations:
If the value of a FAST Motion parameter is changed after logging in, the menu item for creating a boot project will subsequently be deactivated. You need not create a boot project to save the project fail-safe in the controller. An applicative solution is described under 'Short-term measures'.