Corrected from:
PLC Designer V3.15
Response of the new version:
When starting the PLC Designer, the below-described exception no longer occurs.
What happens?
The following exception occurs when starting the PLC Designer:
When does this behaviour occur?
The exception may occur if a third-party software has been installed and, during installation, a version older than V2.1 of the 'Microsoft.Practices.Unity' assembly has been installed in the Windows Global Assembly Cache (GAC).
Which products are affected?
PLC Designer from V3.0
Short-term measures:
Contact the Lenze Service and state the ticket number 8000030907.
Evaluation/recommendations:
The PLC Designer can no longer be started. The function restriction is very rare and cannot be removed by reinstalling the PLC Designer.