Menu command 'Online>Source download to connected device' is deactivated (corrected from V3.18)
Corrected from:
PLC Designer V3.18
Response of the new version:
In multi-controller projects, the source code can be downloaded to the controller - the 'Online>Source download to connected device' menu command is not deactivated.
What happens?
The menu command 'Online>Source download to connected device' is deactivated.
When does this behaviour occur?
The above-described behaviour may occur if a PLC project includes several controllers.
Which products are affected?
PLC Designer from V3.0
Short-term measures:
Use the menu command 'File>Source download' instead of the menu command 'Online>Source download to connected device'. Select the corresponding controller to which you want to download the source code.
Evaluation/recommendations:
In the case of multi-controller projects, the menu command 'Online>Source download to connected device' may be deactivated. If the source code should be downloaded to the controller, see 'Short-term measures' for a remedy.