After changing parameters online no boot project can be created

What happens?
The 'Online>Create boot application for Lenze devices' menu command is deactivated.
 
When does this behaviour occur?
The behaviour may occur when trying to create a boot application in online mode after changing parameters online.
 
Which products are affected?
PLC Designer from V3.3.2
 
Short-term measures:
Log in with the PLC Designer and log off again. As an alternative, change the parameters offline and only go online after all changes have been made.
 
Evaluation/recommendations:
Due to the above function restriction, no boot project can be created when changing parameter values online by using the PLC Designer. For this reason, the changed values will not be saved safe against mains failure in the controller. An applicative solution is described under 'Short-term measures'.