PLC Designer no longer operable when editing comments in the CFC editor
?Corrected from:
PLC Designer V3.27
Behavior of the new version: Regardless of the settings in the 'Options' dialog, comments can be edited in the CFC Editor.
Description of the behaviour:
The PLC Designer is no longer operable when editing comments in the CFC Editor.
Under what conditions does the behaviour occur?
This behavior can occur if the 'Automatically list selection in cross reference view' check box is active in the 'SmartCoding' category of the 'Options' dialog (menu command 'Tools' > 'Options') and the 'Cross-reference List' window (menu command 'View' > 'Cross Reference List') is open.
Affected products: PLC Designer as of V3.13
Short-term measures: Deactivate the switch 'Automatically list selection in cross reference view' in the dialog 'Options'.
Evaluation/Recommendations: When editing comments in the CFC editor, it may happen that the PLC Designer no longer reacts to user inputs. Short-term measures describe a remedy.