Error message when logging in with the PLC Designer (fixed as of V3.21)

Corrected from:
PLC Designer V3.21
 
Response of the new version:
When logging onto a Lenze controller or i950 servo inverter, the error message described below does not appear.
 
Description of the behaviour:
When logging on to a Lenze controller or Servo Inverter i950, the error message appears:
The object reference was not an instance of an object.
 
Under what conditions does the behaviour occur?
This behaviour occurs in rare cases after an existing connection with a Lenze controller or i950 Servo Inverter has been interrupted due to a device restart and the connection is then re-established.
 
Affected products:
PLC Designer V3.0 and higher
 
Short-term measures:
Confirm the error message with <OK>. You can then reestablish the connection.
 
Evaluation/Recommendations:
The functional restriction only leads to minor impairments, since it occurs only rarely (probability of occurrence approx. 1%) and can be remedied by confirming the message.
 
Automartic Translation

URL for linking this AKB article: /en-de/go/akb/201800275/1/