Library repository: Library profile is not fully installed (fixed as of V3.19)

Lifted from:
PLC Designer V3.19
 
behavior of the new version:
If Lenze libraries are installed in the PLC Designer library repository when the PLC Designer is started, the library profile is also automatically installed in full.
 
Description of behavior:
These error messages appear in the PLC Designer message window:
[ERROR]         Symbol Configuration [Device: PLC Logic: Application](Symbol Configuration): C0018:  '__Symbols.T_DUT1._SortedComponents' is no valid assignment target
[ERROR]         Symbol Configuration [Device: PLC Logic: Application](Symbol Configuration): C0004:  '_SortedComponents' is no component of 'TYPEDESC_STRUCT'
 
Under what conditions does the behavior occur? 
A project is compiled with the PLC Designer or a project is transferred to a controller with the PLC Designer.
The project was previously updated to version V3.18 or a project with version V3.18 was created.
The project contains a symbol configuration.
 
Affected products:
PLC Designer as of 3.18.0.11501
 
Short-term measures:
1. Save the following zip file in any directory on your PC:
 
2. Use the context function 'Extract all' (right mouse button) to extract the ZIP file to any directory on your PC. You will then receive the file V3_5_12_61.libraryprofile.
 
3. Select the following menu items in the PLC Designer:
Tools --> Library repository --> Library profiles... --> Import...
2023-12-14 10_35_01-?nderung_im_Engineer_en.jpg

 
4. Select the previously saved file (V3_5_12_61.libraryprofile) and install the library profile.
 
Then the error message described will no longer occur.
 
 
[Automatic Translation]
URL for linking this AKB article: /en-de/go/akb/201900012/1/

Further information