Error message when updating a PLC project with incomplete device description (fixed from V3.19)
Fixed: PLC Designer V3.19
Behavior of the new version:
The project can no longer be updated. A corresponding message appears.
Description of the behaviour:
When updating a device in a PLC Designer project with a newer device description, the following message appears:
Update was done with errors. Take a look into the message window
The error message appears during the subsequent translation:
An error occurs in methode LxDGenerator.CreateFiles
Under what conditions does the behaviour occur?
The described behavior occurs when updating a project that contains an incomplete device description. In this case a tab "Incomplete device description" is displayed when opening the tab of the device.
Affected products:
PLC Designer V3.3 and higher
Short-term measures:
Install the missing device descriptions with the EASY Package Manager. Alternatively, you can insert the affected device into the project with the new version and transfer the settings etc. manually.
Evaluation/Recommendations:
When opening a PLC project, the PLC Designer checks whether the current device descriptions are used in the project and offers the possibility of updating if necessary. If, for example, not all device descriptions for the project are installed on the PC by passing on the project, the behavior described above may occur when the project is updated.