Parameter values are not copied when copying I/O1000 modules

What happens?
When copying an I/O1000 module, the parameter values are not copied. The parameters of the copied module have default setting values.

When does the behaviour occur?
When copying I/O1000 modules on the backplane bus of the c520, c550 and c750 controllers, their parameter values are not copied by the PLC Designer. 

Which products are affected?
PLC Designer from V3.20

Short-term measures:
Adjust the parameter values of the copied I/O1000 modules afterwards.

Evaluation/Recommendations:
During the project planning phase, the I/O1000 modules on the backplane bus of the controller are configured, among other things. If the same I/O module is used several times, the modules can also be copied. In the case of the Lenze controllers c520, c550 and c750, however, their parameter values are not copied. The controllers 3200C and c300 are not affected by this functional restriction.