Device name (parameter 0x2001) is reset (fixed from V3.20)

Correcte from:
PLC Designer V3.20
 
Response of new version:
The device name is no longer reset by pressing the <Set Active Path> button.
 
What happens?
The parameter 0x2001 (device name) is reset to the name entered for the device in the device tree.
 
When does the behaviour occur?
The described behaviour occurs if an active path is set on the communication tab card of the device (press the button < Set active path>).
 
Which products are affected:
PLC Designer as of V3.17
 
Short-term measures:
After setting or changing the active path of the device, check the parameter 0x2001 in the 'Parameter list' tab and adjust it again if necessary.
 
Evaluation / Recommendations: 
The device name can be defined in parameter 0x2001. If the name of the device is changed in the device tree of the PLC Designer, it is automatically entered in parameter 0x2001. If parameter 0x2001 is changed and then the button <Set active path> is pressed, the device name is reset to the name in the device tree.
 
Automatic Translation

URL for linking this AKB article: /en-de/go/akb/201900184/1/