Exception error after switching on the controller (fixed from V3.20.1)
Corrected from: PLC Designer V3.20.1
Response of the new version: No exception error occurs after power on.
What happens?
An exception error (exception) is triggered after restarting the controller.
These entries can be found in the log book:
When does the behaviour occur? A parameter (drive controller or FAST Motion) in the PLC project is changed. No change is made in the PLC program. The project is then transferred and a boot application is generated.
Which products are affected?
PLC Designer V3.20
Short-term measures: 1. In PLC Designer --> trigger "Build --> Clean". 2. Transfer the project with download to the controller. 3. Create boot project 4. Switch the controller to mains --> The boot application starts without an exception error (Exception)
Alternatively, <= V3.19 can be configured with PLC Designer. This function restriction only occurs when using PLC Designer V3.20.0.14652.