Exception error after switching on the controller (fixed from V3.20.1)

Corrected from:
PLC Designer V3.20.1
 
Response of the new version:
No exception error occurs after power on.
What happens?

An exception error (exception) is triggered after restarting the controller.

These entries can be found in the log book:

Exceptions_PLCDesigner.png
 
When does the behaviour occur?
A parameter (drive controller or FAST Motion) in the PLC project is changed. No change is made in the PLC program. The project is then transferred and a boot application is generated.
 
Which products are affected?
PLC Designer V3.20
 
Short-term measures:
1. In PLC Designer --> trigger "Build --> Clean".
2. Transfer the project with download to the controller.
3. Create boot project
4. Switch the controller to mains
--> The boot application starts without an exception error (Exception)

Alternatively, <= V3.19 can be configured with PLC Designer.
This function restriction only occurs when using PLC Designer V3.20.0.14652.
 
Automatic Translation

URL for linking this AKB article: /en-de/go/akb/202000048/1/