Corrected from:
PLC Designer V3.21.1
Response of new version:
Variable values are displayed in the sequence control.
What happens?
No variable values are displayed in the process control.
When does the behaviour occur?
Use of the sequence control in projects created with a compiler version 3.5.12.x or older (up to PLC Designer V3.19) and edited in PLC Designer V3.20.x.
Which products are affected?
PLC Designer (from V3.20.0)
Short-term measures:
By using one of these measures the sequence control can be reused:
1. update the device description of the controller in the project to the current version (V3.18 or higher)
2. update the compiler version in the project to V3.5.14.40 or higher
3. use the older PLC Designer version with which the project was originally created
Evaluation / recommendations:
If the process control can be omitted, no action is required.
The suggested action 3 (use older PLC Designer version) is only recommended if the project is not to be recompiled.