Corrected from:
PLC Designer V3.24
Behavior of the new version:
PDOs of an EtherCAT device with Modular Device Profile can be activated as well as deactivated.
What happens?
A PDO cannot be activated or deactivated.
When does the behaviour occur?
An EtherCAT device with MDP (Modular Device Profile) is used.
An existing PDO ("Process Data" tab) is activated or deactivated.
Example:
Which products are affected?
PLC Designer (from V3.20.0)
Short-term measures:
If the PDO is not needed it can be deactivated via the expert settings.
Alternatively the PLC Desginer V3.19 or older can be used.