What happens?
The error message "Parameter bitX not found. Import not successful!".
When does the behaviour occur?
The import from a CSV file is used to import the variable mapping of a logical I/O of a Safety PLC (C520-S).
Which poducts are affected?
PLC Designer
Short-term measures:
None
Evaluation/Recommendations:
The behaviour is international. Safety IOs may only be entered manually in the Safety Editor. An import is not allowed.
No change is planned for this behaviour.