Undefined placeholder after inserting the recipe manager (corrected from V3.23)

Corrected from:
PLC Designer V3.23

Response of the new version:
If the 'Recipe manager' object is in the PLC Designer project, no undefined placeholder is reported when the project is opened.
 
What happens
When opening a PLC Designer project the dialog 'Project Environment' appears and reports the undefined placeholder 'System_VisuElemBase'.

When does the behaviour occur?
The behavior always occurs when the object 'Recipe Manager' is in the device tree of the PLC Designer project.

Which products are affected?
PLC Designer from V3.22

Short-term measures:
Ignore the message. There is no applicative solution to hide this message.

Evaluation/Recommendations:
The message has no effect on the other behavior of the project and can therefore be ignored. This function restriction also affects the Application Template, since the Recipe Manager is already inserted in the project template.