?Corrected from:
PLC Designer V3.22
Response of the new version:
When importing a parameter set file (*.GDC), all parameters are transferred to the PLC Designer project.
What happens?
With the menu command 'Project' > 'EASY Import' not all parameter values from the selected file with the extension *.GDC are transferred to the PLC Designer project. This affects, for example, the parameters 0x60FF and 0x68FF of an i700 servo inverter connected to the EtherCAT master of the controller.
When does the behaviour occur?
The behaviour described above concerns those parameters that are usually downloaded to the EtherCAT slaves by the Lenze controller when the EtherCAT is started and are therefore typically not stored in the EtherCAT slave.
Which products are affected?
PLC Designer V3.21 and smaller.
Short-term measures:
After importing the parameter set file, check the parameter values and adjust them if necessary.
Evaluation/Recommendations:
When importing a parameter set file (*.GDC) with the command 'EASY Import', not all parameter values are taken over. The parameter values must be checked manually afterwards and adjusted if necessary.
Automatic Translation