Parameter value change after updating a PLC project (corrected from V3.23)
?Corrected from:
PLC Designer V3.23
Response of the new version:
When updating a PLC project, the set parameter values remain unchanged.
What happens?
When updating a PLC project, the parameter values are changed for certain parameters.
When does the behaviour occur?
Based on experience from customer projects, it may become necessary to change the factory setting values of certain Lenze parameters. These parameters are defined in a Lenze library. When updating a PLC project and thus using the new library, the changed factory setting values are entered for the parameters that still have the old factory setting values.
Which products are affected?
PLC Designer ab V3.0
Short-term measures:
After updating a PLC project, check the parameter values set in the project and correct them if necessary.
Evaluation / recommendations:
This function restriction can occur if Lenze has published new library versions and an existing PLC project is updated and thus the new library is used. This may change the parameter values of certain parameters in the PLC project.