Corrected from:
PLC Designer V3.24
Behavior of the new version:
Visualization elements can change the position in the way defined in the 'Relative motion' or 'Absolute motion' property.
What happens?
For a visualization element (e.g. element 'Line'), the position is defined via the property 'Relative movement' or 'Absolute movement' in order to change the position during runtime via a PLC variable. However, the change of this movement remains without effect. The visualisation element does not change its position when the value of the PLC variable in the movement property changes.
When does the behaviour occur?
The behaviour occurs if the specific profile 'CODESYS V3.5 SP16' is set in the 'Visualization Profile' category in the 'Project Settings' dialogue (menu command 'Project' > 'Project Settings').
Which products are affected?
PLC Designer from V3.22
Short-term measures:
Set the specific profile 'CODESYS V3.5 SP15 Patch 5' in the 'Visualization Profile' category in the 'Project Settings' dialogue.
Evaluation/Recommendations:
The function can be restored by selecting an older visualization profile. Visualization functions that are only available from the 'CODESYS V3.5 SP16' profile cannot be used.