PLC Designer: Visualisation error messages after new installation (corrected from V3.26)

Corrected from:
PLC Designer V3.26.0

Response of the new version:
After installing the current version of the PLC Designer, the restriction described below no longer occurs - visualisation pages are displayed correctly and can be created or edited.

What happens?
The following error messages appear when translating a project:
  • Could not open library '#System_Visu[xxx]'. (Reason: The placeholder library [xxx] could not be resolved.)
  • Visualisation elements are missing on visualisation pages in the PLC Designer project.
  • The tab 'Visualisation tools' does not contain any visualisation elements.
It is no longer possible to create or edit a visualisation page.
Existing visualisation pages are not displayed correctly.

When does the behaviour occur?
The behaviour can occur sporadically after the installation of a PLC Designer.

Which products are affected?
PLC Designer

Short-term measures:
Execute the following setups again directly:
- \Prerequisites\SetupModules\PlcDesigner.Repository.Setup.msi
- \Prerequisites\SetupModules\PlcDesigner.RepositoryVisu.Setup.msi

Evaluation / recommendations:

Automatic Translation

URL for linking this AKB article: /en-de/go/akb/202100258/1/