Error message 'The logical device “xxx” is mapped to more than one device' when compiling

Corrected from:
-

Response of the new version:
-
 
What happens?
When compiling the PLC project, the error message appears:
The logical device "xxx" is mapped to more than one device. 

When does the behaviour occur?
The error message described above occurs when the safety I/O modules were transferred to the PLC project by means of a bus scan and were subsequently renamed.

Which products are affected?
PLC Designer

Short-term measures:
Insert the safety I/O modules manually into the PLC project.

Evaluation / recommendations:
This function restriction can occur during the project planning phase and will be detected at the latest during the project download.


Automatic Translation

URL for linking this AKB article: /en-de/go/akb/202200253/1/