x750: Black exclamation mark when using an EPM-S110

What happens?
When starting an EPM-S110 IO module on the CAN bus of a Gateway x750, black exclamation marks appear.
Schwarzes_Asusrufungszeichen.png
There is an error message in the logbook.
Log_zu_schwarzem_Ausrufungszeichen.png

When does the behaviour occur?
When starting a CAN bus with EtherCAT/CAN gateway x750 to which the IO1000 module EPM-S110 is connected.
 
Which products are affected?
Gateway EtherCAT/CAN x750 (all versions)

Short-term measures:
The black exclamation marks can be ignored. The IO module is in Operational.

Alternatively, the boot-up timeout for EPM-S110 can be increased to 10s.
Ideally, the setting should be executed in the system events "StartDone" and "ResetDone".
Example:
SetBootupTimeout.png

Evaluation / recommendations:
No remedy is planned for this behaviour.


Automatic Translation

URL for linking this AKB article: /en-de/go/akb/202200352/1/