No reaction when opening the CODESYS Package Manager

Corrected from:
-

Response of the new version:
-
 
What happens?
Clicking on the menu command 'Tools' > 'CODESYS Package Manager' has no function. The CODESYS Package Manager dialogue does not open.

When does the behaviour occur?
If the 'CODESYS Development System V3' with Service Pack 18 or higher was installed on the PC, then the call of the CODESYS Package Manager from the PLC Designer is deactivated
  
Which products are affected?
PLC Designer from V3.0
 
Short-term measures:
Uninstall the 'CODESYS Installer' program from your PC. It is still possible to run the 'CODESYS Development System V3' after uninstallation.
 
Evaluation / recommendations:
The parallel installation of the PLC Designer and the CODESYS Development System V3 can lead to the CODESYS Package Manager no longer being able to be opened in the PLC Designer. The CODESYS Package Manager is required to install packages from the CODESYS Store, such as CODESYS SVN, in the PLC Designer.