Application Template: Bus cycle task not set - error message 20662

Corrected from:

Response of the new version:
 
What happens?
A multitask project (e.g. Basis Application Template) is used. In it, a counter module is connected to an EPM-S131. An LM_FreeEncoder_ECAT was attached to the counter module.
On start-up, error message 20662 - Initialisation error on encoder backplane bus.

When does the behaviour occur?
A multitask project (e.g. project template L_FAST_Standard) is used and, for example, an EPM-S131 with a counter module is connected. The counter module is assigned the TaskFreewheeling, which leads to error message 20662. 
 
Which products are affected?
PLC Designer from V3.24
Application Template

Short-term measures:
The "TaskHighPriority" must be assigned to the bus cycle task in the PLC settings.
Workaround_202200378.png
 
Evaluation / recommendations:


Automatic Translation

URL for linking this AKB article: /en-de/go/akb/202200378/1/