Corrected from:
PLC Designer V3.27
Response of the new version:
The menu commands necessary for the operation of the Application Tempate (L_FAST_Standard) are displayed.
What happens?
All menu items of the application template (L_FAST_Standard) are not displayed.
When does the behaviour occur?
The behaviour described above occurs when creating a new PLC project based on the Application Template and when opening a project created with an older PLC Designer version.
Which products are affected?
PLC Designer from V3.26
Short-term measures:
- Open the 'Customise' dialogue (menu command 'Tools' > 'Customise').
- Save the current menu configuration by clicking the <Save> button.
- Then load the file 'AT.opt.menu' attached to this article. This will overwrite any changes previously made in the PLC Designer menu!
Evaluation / recommendations:
Due to this function restriction, the Application Template can no longer be edited comfortably in the PLC Designer. An application solution is described under Short-term measures.