Safety: No assignment of the FSoEMaster function block possible for safety devices

Removed from:
PLC Designer V4.0.1
Behavior of the new version:
When selecting the instance name for the function block FSoEMaster, all entries under 'Logical I/Os' are displayed.

Description of the behavior:
The FSoEMaster function block can be added to a safety POU. The list for assigning the function block to a safety device (Logical I/Os) is empty.
PLCD4_FSoEMaster_SSHOT.png

Conditions under which the behavior occurs:
The behavior described above occurs when a Safety Controller c250-S in the PLC Designer V4.0, a c250-S safety controller is inserted into the PLC project as an EtherCAT slave.

Affected products:
PLC Designer as of V4.00

Short-term measures, Recommendations,Rating:
Manually enter the identifier of the logical I/O as the instance name of the FSoEMaster function block.

[Automatic Translation]