Safety: No assignment of the FSoEMaster function block possible for safety devices
Removed from:
PLC Designer V4.0.1
Behavior of the new version:
When selecting the instance name for the function block FSoEMaster, all entries under 'Logical I/Os' are displayed.
Description of the behavior: The FSoEMaster function block can be added to a safety POU. The list for assigning the function block to a safety device (Logical I/Os) is empty.
Conditions under which the behavior occurs: The behavior described above occurs when a Safety Controller c250-S in the PLC Designer V4.0, a c250-S safety controller is inserted into the PLC project as an EtherCAT slave.
Affected products: PLC Designer as of V4.00
Short-term measures, Recommendations,Rating: Manually enter the identifier of the logical I/O as the instance name of the FSoEMaster function block.